LC1D09M7 - SCHNEIDER Electric Contractor 25A 220V TeSys D Kontaktor - 3P(3 NO) - AC-3 - <= 440 V 9 A - 220 V AC coil

Rp 405.500,00 Rp 1.000.000,00
59
Atau lihat kebijakan pengiriman kami

Tax included. Shipping calculated at checkout.

100 in stock
Delivery:
Estimated delivery time: 5-7 days
Returns:
Within 45 days of purchase
Sku:
4
Payment & Security
Visa Mastercard American Express PayPal Diners Club Discover

Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.

Note: Harga Belum termasuk PPN 11%

Spesifikasi dan Deskripsi SCHNEIDER Electric LC1D09M7 Contractor 25A 220V TeSys D Kontaktor - 3P(3 NO) 

Kontaktor LC1D09M7 adalah bagian dari lini produk TeSys Deca (sebelumnya TeSys D) dari Schneider Electric, yang merupakan salah satu seri kontaktor paling populer di dunia karena keandalan dan fleksibilitasnya. Kontaktor ini dirancang untuk aplikasi kontrol motor dan beban umum. Kelebihannya:

  • Tampilan dan nuansa modern baru untuk semua mesin
  • Dirancang untuk memenuhi persyaratan aplikasi industri dan HVAC
  • Lebih mudah dipasang dan dioperasikan dengan sekrup multi-standar
  • Dengan kepatuhan IEC60335-1, peningkatan ketahanan api, dan aksesori anti-debu
  • Pengalaman pelanggan digital untuk dokumen teknis

Kontaktor TeSys D, 3 kutub (3NO), untuk aplikasi kontrol motor hingga 9A/690V AC-3/3e (4kW@400V). Ini menyediakan koil AC 220V 50 / 60Hz, kontak tambahan bawaan 1NO + 1NC (NC mirror certified), koneksi dengan terminal penjepit sekrup. Untuk tingkat pengoperasian hingga 3600 siklus/jam dan lingkungan hingga 60°C, ini menghasilkan keandalan dan daya tahan tinggi untuk aplikasi yang menuntuk performa tinggi. Bentuk yang kompak (lebar 45mm), pemasangan DIN-rail atau pemasangan sekrup. Bersertifikat multi standar (IEC, UL, CSA, CCC, EAC, Marine).

    Range of product TeSys Deca
    Product or component type Contactor
    Device short name LC1D
    Contactor application Motor control
    Resistive load
    Utilisation category AC-4
    AC-3
    AC-1
    AC-3e
    Poles description 3P
    [Ue] rated operational voltage Power circuit: <= 690 V AC 25...400 Hz
    Power circuit: <= 300 V DC
    [Ie] rated operational current 9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
    25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
    9 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
    [Uc] control circuit voltage 220 V AC 50/60 Hz
    Complementary
    Motor power kW 2.2 kW at 220...230 V AC 50/60 Hz (AC-3)
    4 kW at 380...400 V AC 50/60 Hz (AC-3)
    4 kW at 415...440 V AC 50/60 Hz (AC-3)
    5.5 kW at 500 V AC 50/60 Hz (AC-3)
    5.5 kW at 660...690 V AC 50/60 Hz (AC-3)
    2.2 kW at 400 V AC 50/60 Hz (AC-4)
    2.2 kW at 220...230 V AC 50/60 Hz (AC-3e)
    4 kW at 380...400 V AC 50/60 Hz (AC-3e)
    4 kW at 415...440 V AC 50/60 Hz (AC-3e)
    5.5 kW at 500 V AC 50/60 Hz (AC-3e)
    5.5 kW at 660...690 V AC 50/60 Hz (AC-3e)
    Motor power hp 1 hp at 230/240 V AC 50/60 Hz for 1 phase motors
    2 hp at 200/208 V AC 50/60 Hz for 3 phases motors
    2 hp at 230/240 V AC 50/60 Hz for 3 phases motors
    5 hp at 460/480 V AC 50/60 Hz for 3 phases motors
    7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors
    0.33 hp at 115 V AC 50/60 Hz for 1 phase motors
    Compatibility code LC1D
    Pole contact composition 3 NO
    Protective cover With
    [Ith] conventional free air thermal current 25 A (at 60 °C) for power circuit
    10 A (at 60 °C) for signalling circuit
    Irms rated making capacity 250 A at 440 V for power circuit conforming to IEC 60947
    140 A AC for signalling circuit conforming to IEC 60947-5-1
    250 A DC for signalling circuit conforming to IEC 60947-5-1
    Rated breaking capacity 250 A at 440 V for power circuit conforming to IEC 60947
    [Icw] rated short-time withstand current 105 A 40 °C - 10 s for power circuit
    210 A 40 °C - 1 s for power circuit
    30 A 40 °C - 10 min for power circuit
    61 A 40 °C - 1 min for power circuit
    100 A - 1 s for signalling circuit
    120 A - 500 ms for signalling circuit
    140 A - 100 ms for signalling circuit
    Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
    25 A gG at <= 690 V coordination type 1 for power circuit
    20 A gG at <= 690 V coordination type 2 for power circuit
    Average impedance 2.5 mOhm - Ith 25 A 50 Hz for power circuit
    Power dissipation per pole 1.56 W AC-1
    0.2 W AC-3
    0.2 W AC-3e
    [Ui] rated insulation voltage Power circuit: 690 V conforming to IEC 60947-4-1
    Power circuit: 600 V CSA certified
    Power circuit: 600 V UL certified
    Signalling circuit: 690 V conforming to IEC 60947-1
    Signalling circuit: 600 V CSA certified
    Signalling circuit: 600 V UL certified
    Overvoltage category III
    Pollution degree 3
    [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
    Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
    Mechanical durability 15 Mcycles
    Electrical durability 0.6 Mcycles 25 A AC-1 at Ue <= 440 V
    2 Mcycles 9 A AC-3 at Ue <= 440 V
    2 Mcycles 9 A AC-3e at Ue <= 440 V
    Control circuit type AC at 50/60 Hz standard
    Coil technology Without built-in suppressor module
    Control circuit voltage limits 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
    0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
    0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
    1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
    Inrush power in VA 70 VA 60 Hz cos phi 0.75 (at 20 °C)
    70 VA 50 Hz cos phi 0.75 (at 20 °C)
    Hold-in power consumption in VA 7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
    7 VA 50 Hz cos phi 0.3 (at 20 °C)
    Heat dissipation 2…3 W at 50/60 Hz
    Operating time 12...22 ms closing
    4...19 ms opening
    Maximum operating rate 3600 cyc/h at 60 °C
    Connections - terminals Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
    Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
    Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
    Power circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
    Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
    Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
    Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
    Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
    Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
    Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
    Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
    Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
    Tightening torque Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
    Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
    Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
    Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
    Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
    Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
    Auxiliary contact composition 1 NO + 1 NC
    Auxiliary contacts type type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
    type mirror contact 1 NC conforming to IEC 60947-4-1
    Signalling circuit frequency 25...400 Hz
    Minimum switching voltage 17 V for signalling circuit
    Minimum switching current 5 mA for signalling circuit
    Insulation resistance > 10 MOhm for signalling circuit
    Non-overlap time 1.5 ms on de-energisation between NC and NO contact
    1.5 ms on energisation between NC and NO contact
    Mounting support Plate
    Rail
    Environment
    Standards CSA C22.2 No 14
    EN 60947-4-1
    EN 60947-5-1
    IEC 60947-4-1
    IEC 60947-5-1
    UL 60947-4-1
    IEC 60335-1:Clause 30.2
    IEC 60335-2-40:Annex JJ
    UL 60335-2-40:Annex JJ
    CSA C22.2 No 60947-4-1
    Product certifications UL
    CCC
    CSA
    Marine
    UKCA
    EAC
    CB Scheme
    IP degree of protection IP20 front face conforming to IEC 60529
    Protective treatment TH conforming to IEC 60068-2-30
    Climatic withstand conforming to IACS E10 exposure to damp heat
    conforming to IEC 60947-1 Annex Q category D exposure to damp heat
    Permissible ambient air temperature around the device -40…60 °C
    60…70 °C with derating
    Operating altitude 0...3000 m
    Fire resistance 850 °C conforming to IEC 60695-2-1
    Flame retardance V1 conforming to UL 94
    Mechanical robustness Vibrations contactor open (2 Gn, 5...300 Hz)
    Vibrations contactor closed (4 Gn, 5...300 Hz)
    Shocks contactor open (10 Gn for 11 ms)
    Shocks contactor closed (15 Gn for 11 ms)
    Height 77 mm
    Width 45 mm
    Depth 86 mm
    Net weight 0.32 kg
    Vendor AMS Network
    Type electricity
    Sku 4
    Weight 0.8 kg